Power Transducers
- Power Factor Transducer
- Input 3-phase voltage & current
- Output Single or Dual (DC)
- Accuracy 0.5%
Operations The input Voltage and current signals are scaled down through interposing and cur rent transformers. The scaled down voltage signal proportional to vcosÃË. This signal is divided by the voltage signal to get DC Voltage linearly proportional to Power Factor. This output is further processed to provide DC Voltage / Current output signal.
The Transducer is suitable for balanced load conditions only, when used on 3 Phase 3 Wire, 3 Phase 4 Wire electrical networks. Technical Specifications
- Auxiliary Supply: Self Powered, 110/240 V AC, 24 / 48 / 110 / 220 V DC + 20 %
- Power Consumption: 3.5 VA - AC, 4 VA - DC
- Input Value
- I in: 1 A / 5 A
- V in: 110 / 415 V
- DC Output (Single / Dual):0 - 1 mA, 0 - 10 mA, 0 - 20 mA, 4 - 20 mA, 0 - 5 V, 0 - 10 V
- No of Signal Output: Single (Optional Dual Output)
- Response Time: Less than 500 milliseconds
- Input / Output isolation: Galvanic
- Temperature: 0oC to + 55oC
- Humidity: Up to 95% Rh non condensing
- Dimensions (L x W x D) (mm): 73 x 150 x 113
- Weight: 1200 gms.
Common Specifications
Output Load Resistance (Rout)
- For Current Output: Max. 10V/I out (Optional Max. 15V/Iout)
- For Voltage Output: 10 Kohm (min.)
Output Ripple: Less than 0.5% of span (peak to peak) Auxiliary Supply Burden: Less than 4 VA Insulation Resistance: More than 100 Mohms at 500 V DC Zero Span Adjustment: Optionally provided Terminals: Suitable for 2.5 sq.mm wires Enclosure Type: ABS Plastic, Ingress Protection IP40 Applications Suitable For Following Applications
- Control & Relay Panel
- Metering Panels
- Motor Testing Equipments
- Transformer Panels
- Cogeneration /Captive Power Plants
- Paper Mills, Sugar Plant
|